SECTION 2 – OPTIVIEW CONTROL CENTER
CYCLING SHUTDOWN - AUTO RESTART
VSD #2 - SERIAL COMMUNICATIONS

FIGURE 26 - MOTOR STARTER SCREEN

This screen displays information pertaining to the
Motor Starter.
DISPLAY ONLY
Lead Compressor
Displays whether compressor 1 or compressor 2 is the
lead compressor.
Motor Run (LED)
Separate indication showing whether the digital output
from the controls is commanding motor 1 or motor 2
to RUN.
% Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value for motor 1 and motor 2.
Motor Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0 to 20 mA, 4 to 20 mA, 0 to 10 VDC or
2 to 10 VDC input in Analog Remote mode, PWM sig-
nal in Digital Remote mode, SC-EQ communications
interface in ISN (BAS) mode, or a locally programmed
value.
78

MOTOR STARTER SCREEN

Operating Hours
Individually indicates the total number of hours com-
pressor 1 and compressor 2 have run.
Number of Starts
Individually indicates the total number of times com-
pressor 1 and compressor 2 have started.
Motor Heater (LED)
Indicates whether the digital output from the controls
is commanding the optional motor heater on for each
motor. This LED is not displayed if the option is not
installed.
PROGRAMMABLE
Local Chiller Current Limit
Access Level Required: OPERATOR
Sets the maximum current draw of the chiller when run
in the Local Mode. This is the total current of motor 1
and motor 2 added together. (Adjustable between 30
and 100%, Default = 100%)