SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

FIGURE 23 - ECONOMIZER VGD SETPOINTS SCREEN

OVERVIEW
This screen displays information for the Economizer
VGD Setpoints information. Also, the Economizer VGD
Setpoints can be changed from this screen.
DISPLAY ONLY
Stall Detector Voltage
Displays the Stall Detector output voltage as received
by the Microboard.
High Limit
Displays the voltage. If the voltage is exceeded the
VGD will close to prevent the unit from stalling.
Low Limit
Displays the voltage, that if has dropped below the
setpoint, will cause the VGD to open, allowing more
gas through the compressor.
Mach Number
Displays the speed of the refrigerant gas leaving the
compressor in percentage of Mach (the speed of sound).
62

ECONOMIZER VGD SETPOINTS SCREEN

VGD Closed Limit Switch
Displays the status of the VGD Limit Switch. Dis-
played as CLOSED when the switch is closed. This
would be when the VGD is in the fully closed position.
Otherwise, displayed as OPEN.
VGD Opening (LED)
Illuminates when a close signal is being applied to the
VGD.
VGD Closing (LED)
Illuminates when an open signal is being applied to the
VGD.
Stall Count
Displays the number of times that the system had de-
tected an Economizer Compressor Stall.
Stall Time
Displays the accumulated time that the Stall Detector
Board output is greater than the High Limit Setpoint
voltage while the chiller is running.
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
LD19634