Harmonic Filter Details Screen; Figure 44 - Harmonic Filter Details Screen - York YK-EP B Operation & Maintenance Manual

With optiview control center solid state starter and variable speed drive
Table of Contents

Advertisement

FORM 160.87-OM1
ISSUE DATE: 8/24/2018

FIGURE 44 - HARMONIC FILTER DETAILS SCREEN

OVERVIEW
This screen displays more detailed information per-
taining to the IEEE-519 Harmonic Filter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the Variable Speed Drive
this is the data returned by the VSD Logic Board.
Current Limit Setpoint
Displays the current limit value in use. This value
could come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC
or 2 to 10VDC input in Analog Remote mode, PWM
signal in Digital Remote mode, E-Link or SC-EQ com-
munications interface in ISN mode, or a locally pro-
grammed value.
JOHNSON CONTROLS

HARMONIC FILTER DETAILS SCREEN

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Operating Mode (Run / Stop)
Indicates whether the Harmonic Filter is operating.
VSD Model
Access Level Required: SERVICE
Displays the horsepower for which the attached Har-
monic Filter is configured.
DC Bus Voltage
Displays the DC Bus voltage as measured by the Har-
monic Filter.
Supply Contactor (LED)
Indicates whether the output to the Supply Contactor
is energized.
LD15431
105
2