Updating the firmware
8

Updating the firmware of the peripheral devices

8.2 Updating the firmware of the peripheral devices

8.3 Converting a station

112 | 412
Building Technologies
Fire Safety
You can update the firmware of the following peripheral devices:
Floor repeater terminal FT2010
Floor repeater display FT2011
Radio gateway FDCW221
Mimic display driver FT2001-A1
MCL-USB adapter FDUZ221
Line tester FDUL221
To connect a peripheral device to the PC, you need the MCL-USB adapter.
You will find more information in document A6V10210416. See chapter 'Applicable
documents'.
See also
2 Applicable documents [➙ 13]
The 'Replace element' function is used to convert a configuration from a small
station type to a larger station type.
The following conversions are possible:
FC722 to FC723 or FC724 or FC726
FC723 to FC726
FC724 to FC726
The possible conversions are determined by the ↑ BDV used and may differ from
those shown above.
How to convert a ↑ 'Station'
w A 'Station' of type FC722, FC723 or FC724 is available.
1. Select the 'Station' to be converted.
2. In the menu, click on 'Edit' > 'Replace element'.
3. Select the target station type for the conversion.
4. Confirm your selection with 'Yes'.
a The configuration of the 'Station' has been converted.
Conversion log
The critical conversions are logged for the converted 'Station'. The logs can be
viewed in the 'Conversion log' window or printed from the log file.
A6V10210424_j_en_--
2018-08-29