Behavior In Degraded Mode; Interface To Service Devices - Siemens FDOOTC241 Technical Manual

Neural fire detector
Hide thumbs Also See for FDOOTC241:
Table of Contents

Advertisement

Structure and function
3
Function

3.3.11 Behavior in degraded mode

3.3.12 Interface to service devices

38 | 94
Building Technologies
Fire Safety
Applicable for the FDnet:
When the main processor of the fire control panel fails, the control panel works in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.
Degraded mode operation behavior on control panels that support
degraded mode operation:
Alarming is still ensured in degraded mode operation. However, in degraded
mode only collective alarming is possible. This means that in the event of an
alarm, it is possible to identify the detector line but not the exact location of the
detector triggering the alarm.
If a sounder base is connected to the output for the external alarm indicator, it
is activated in degraded mode operation if there is a fire alarm (only with
detectors and sounder bases with ES 30). Configuration for a specific control
panel is possible.
When the connection for the external alarm indicator is used for a control
function (e.g. hold-open system), the output assumes the configured fail-safe
position; configuration for a specific control panel is possible.
In degraded mode operation, the FDOOTC241 only supports the 'Fire' alarm
class. If the 'CO' alarm class is also to be supported in degraded mode operation,
technical customer support must be informed.
Degraded mode operation on the FDnet is not supported in the same way by all
control panels. The information in the 'List of compatibility' and in the corresponding
control panel documentation must be taken into account during project planning.
A proximity interface (MC link) is available for commissioning and maintenance in
order to communicate with the detector exchanger and tester FDUD292 and the
intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.