Settings And Displays For Profienergy In The Inverter - Siemens SINAMICS G110M Function Manual

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via PROFIBUS and PROFINET
3.4 Communication via PROFINET
3.4.4.3

Settings and displays for PROFIenergy in the inverter

Pause time
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
– When the pause time is less than p5602[1], the inverter rejects the command
● Maximum pause time: p5606
Inhibiting PROFIenergy
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter rejects the "Start_Pause" command with 50 hex (no
appropriate pause mode).
Transition into the energy-saving mode from the PROFIdrive states ready (S3) and operation (S4)
If you set p5611.2 = 1, you allow the transition into the energy-saving mode from the
PROFIdrive states ready (S3) and operation (S4).
To do so, you must set one of the following settings:
● p5611.1 = 1: With the transition to the energy-saving mode, the inverter issues an OFF1
command and enters the start-inhibit state (S1).
● p5611.1 = 0: You can use p5614 to interconnect a signal source that switches the inverter
off and places it in the start inhibited state (S1).
If the control sends the command "End_Pause" or "Start_Pause" with a pause time of 0, then
the inverter does not restart, even if the appropriate enable signals are still set.
An OFF1/on command is required in order that the inverter restarts.
PROFIenergy measured values
PROFIenergy
Measured value
ID
Name
34
Active power
166
Power factor
200
Active energy import
64
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
"Start_Pause" with 50 hex (no appropriate pause mode).
Accuracy
Unit
Domain
Class
1
12
W
1
12
1
2
11
Wh
SINAMICS source parameters
Number
Name
r0032
Active power smoothed
r0038
Smoothed power factor
r0039[1]
Energy accepted
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Range of
values
r2004
0 ... 1
-
Fieldbuses

Advertisement

Table of Contents
loading

Table of Contents