Siemens SINAMICS G110M Function Manual page 48

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via PROFIBUS and PROFINET
3.1 PROFIdrive profile
Note
Precondition for diagnostics via PROFIBUS
The master must operate in the DPV1 mode for diagnostics via Profibus.
Default diagnostics
The following values are decisive for the diagnostics:
Ext_Diag: Group signal for diagnostics in the slave:
- 0: No fault is active
- 1: At least one alarm or fault is active
Ext_Diag_Overflow:
Display for the diagnostics overflow in the slave (for more than 240 bytes)
Identifier-related diagnostics
The identifier-related diagnostics provides a bit (KB_n) for each slot allocated when configuring the
device. If a diagnostics message is active at a slot, then it's KB_n = 1.
For G120 only one slot is allocated:
KB_0 when configuring with the GSD
KB_3 when configuring with the object manager
48
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Fieldbuses