Uss Parameter Channel - Siemens SINAMICS G110M Function Manual

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via RS485
5.3 Communication via USS
5.3.4

USS parameter channel

Structure of the parameter channel
Depending on the setting in p2023, the parameter channel has a fixed length of three or four
words, or a variable length, depending on the length of the data to be transferred.
1. and 2nd word contain the parameter number and index as well as the type of job (read or
write). The other words of the parameter channel contain parameter contents. The
parameter contents can be 8-bit values, 16-bit values (such as baud rate) or 32-bit values
(e.g. CO parameters). The parameter contents are entered right justified in the word with the
highest number. Words that are not required are assigned 0.
Bit 11 in the 1st word is reserved and is always assigned 0.
The diagram shows a parameter channel that is four words long.
You can find examples of telegrams at the end of this section.
Request and response IDs
Bits 12 ... 15 of the 1st word of the parameter channel contain the request and response
identifier.
Table 5- 4
Request identi-
fier
0
1
2
3
4
6
2)
7
2)
8
2)
9
The required element of the parameter is specified in IND (2nd word).
1)
The following request IDs are identical: 1 ≡ 6, 2 ≡ 7 3 ≡ 8.
2)
We recommend that you use identifiers 6, 7, and 8.
112
Request identifiers, control → inverter
Description
No request
Request parameter value
Change parameter value (word)
Change parameter value (double word)
Request descriptive element
Request parameter value (field)
Change parameter value (field, word)
Change parameter value (field, double word)
Request number of field elements
1)
1)
1)
1)
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Response identifier
positive
negative
0
7 / 8
1 / 2
7 / 8
1
7 / 8
2
7 / 8
3
7 / 8
4 / 5
7 / 8
4
7 / 8
5
7 / 8
6
7 / 8
Fieldbuses

Advertisement

Table of Contents
loading