Siemens SINAMICS G110M Function Manual page 127

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

The process data are transferred into the register range from 40100 up to 40111.
Note
R"; "W"; "R/W" in the column Modbus access stands for read (with FC03); write (with FC06);
read/write.
Table 5- 11
Assigning the Modbus register to the parameters of the Control Unit
Modbus
Description
register
number
Process data
Control data
40100
Control word
you can find additional information in
function diagram 9342 in the List Ma-
nual of your inverter.
Overview of the manuals (Pa-
ge 235)
40101
Main setpoint
Status data
40110
Status word
you can find additional information in
function diagram 9352 in the List Ma-
nual of your inverter.
Overview of the manuals (Pa-
ge 235)
40111
Main actual value
Parameter data
Digital outputs
40200
DO 0
40201
DO 1
40202
DO 2
Analog outputs
40220
AO 0
40221
AO 1
40523
AO 0
40524
AO 1
Digital inputs
40240
DI 0
40241
DI 1
40242
DI 2
40243
DI 3
Fieldbuses
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Modb
Unit
Scaling
us
factor
ac-
cess
R/W
--
1
R/W
--
1
R
--
1
R
--
1
R/W
--
1
R/W
--
1
R/W
--
1
R
%
100
R
%
100
R/W
%
100
R/W
%
100
R
--
1
R
--
1
R
--
1
R
--
1
Communication via RS485
5.4 Communication using Modbus RTU
ON/OFF text
Data / parameter
or Value range
Process data 1
Process data 2
Process data 1
Process data 2
HIGH
LOW
p0730, r747.0, p748.0
HIGH
LOW
p0731, r747.1, p748.1
HIGH
LOW
p0732, r747.2, p748.2
-100.0 ... 100.0
r0774.0
-100.0 ... 100.0
r0774.1
-199.99 ... 199.99 p0791.0
-199.99 ... 199.99 p0791.1
HIGH
LOW
r0722.0
HIGH
LOW
r0722.1
HIGH
LOW
r0722.2
HIGH
LOW
r0722.3
127