Connection
5.1 Line and motor connection
5.1.6

Inverter terminals

Table 5- 3
Connection type, cable cross sections and tightening torques
Inverters
Connection
FSC
Line cable, motor cable
and braking resistor
FSD
Line cable, motor cable
and braking resistor
FSE
Line cable, motor cable
and braking resistor
FSF
Line cable, motor cable
and braking resistor
The cross-sections specified refer to possible cable cross-sections for the terminals, not for the current that you require for
your particular application.
5.1.7

Establishing connections

Establishing the line and motor connection, frame size FSA
The terminals are directly accessible.
Connect the line cable phases to terminals L1, L2, L3 and the protective conductor to PE.
Connect the motor cable phases to terminals U2, V2, W2 and the protective conductor to
.
36
Cross-section and tightening torque
Metric
Terminal
4 ...10 mm: 2.3 Nm
Cable
10 ... 35 mm
: 6 Nm
2
lug
Cable
25 ... 35 mm
: 6 Nm
2
lug
Cable
35 ... 120 mm
2
lug
12 ... 8 AWG: 20 lbf in
7 ... 2 AWG: 53 lbf in
3 ... 2 AWG: 53 lbf in
: 13 Nm
2 ... 4/0 AWG: 115 lbf in
Hardware Installation Manual, 01/2016, A5E36265179B-AA
Strip
lengths
Imperial
10 mm
--
--
--
PM250 Power Module