Read Parameter - Siemens SINAMICS G110M Function Manual

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via RS485
5.4 Communication using Modbus RTU
5.4.6.1

Read parameter

Example: r0002 read acyclically
Table 5- 18
Write parameter request: Reading the parameter value of r0002 from slave number 17
Byte
Description
Header
11 h
0
Slave address
10 h
1
Function code (write multiple)
0258 h
2,3
Register start address
0007 h
4,5
Number of registers to be read (40601 ... 40607)
0E h
6
Number of data bytes (7 registers, each 2 bytes = 14 bytes)
User data
0001 h
7,8
40601: DS47 Control = 1 (activate request)
2F0A h
9,10
40602: Function 2F h (47), request length 10 bytes (0A h)
8001 h
11,12
40603: Request reference = 80 h, request identifier = 1 h
0101 h
13,14
40604: DO-Id = 1, number of parameters = 1
1001 h
15,16
40605: Attribute, number of elements = 1
0002 h
17,18
40606: Parameter number = 2
0000 h
19,20
40607: Subindex = 0
Table 5- 19
Start parameter request: Reading the parameter value of r0002 from slave number 17
Byte
Description
11 h
0
Slave address
03 h
1
Function code (read)
0258 h
2,3
Register start address
0007 h
4,5
Number of registers to be read (40601 ... 40607)
0010 h
6,7
Number of registers
Table 5- 20
Response for successful read operation
Byte
Description
Header
11 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
03 h
1
Function code (read)
20 h
2
User data
0002 h
3,4
40601: DS47 Control = 2 (the request was executed)
2F08 h
5,6
40602: Function code 2F h (47), response lengths 8 bytes
8001 h
7,8
40603: Request reference mirrored = 80 h,
response identifier = 1 (request parameter)
0101 h
9,10
40604: DO-ID = 1, number of parameters = 1
0301 h
11,12
40605: Format, number of elements = 1
001F h
13,14
40606: Parameter value = 1F h (31)
134