Quick Commissioning Through The Parameter Menu - Siemens SINAMICS V20 Series Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20 Series:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning
Parameter
Access
level
P1003[0]
2
P2201[0]
2
P2202[0]
2
P2203[0]
2
5.5.2

Quick commissioning through the parameter menu

As an alternative to quick commissioning through the setup menu, commissioning using the
parameter menu provides the other solution for quick commissioning. This would be helpful
for those who are used to commissioning the inverter in this way.
Setting parameters
NOTICE
In the table below, "●" indicates that the value of this parameter must be entered according
to the rating plate of the motor.
Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0100
50 / 60 Hz selection
P0304[0] ●
Rated motor voltage [V]
56
Function
Fixed frequency setpoint 3
Fixed PID frequency setpoint 1
Fixed PID frequency setpoint 2
Fixed PID frequency setpoint 3
Setting
= 3 (Expert access level)
= 1 (quick commissioning)
Set a value, if necessary:
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
Range: 10 ... 2000
Note:
The input of rating plate data must correspond with the wiring of
the motor (star / delta)
Text menu
(if P8553 = 1)
(FIX F3)
(PID F1)
(PID F2)
(PID F3)