Temperature Protection; Error Information; Boiler History - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

13

TEMPERATURE PROTECTION

The difference between Supply temperature and Return Temperature is continuously monitored. A too big
difference can indicate a defective pump or a clogged heat exchanger. To protect the boiler, the burner controller
reduces the input when the temperature difference ∆T becomes too high:
At maximum boiler input ∆T is limited to 63 °F (35 °C) (Hx_Diff_DeltaT_Min).
In between 63 °F (35 °C) and 77 °F (43 °C) boiler input modulates between minimum and maximum.
At minimum boiler input ∆T above 77 °F (43 °C) is allowed (Hx_Diff_DeltaT_Min
Above ∆T = 86 °F (48 °C), the boiler is switched OFF during HX_Diff_Max_Wait_Time.
Relevant factory set variables
Parameter
HX Diff DeltaT Min
HX Diff Max Wait Time
Wait time after upper limit primary heat exchanger differential has been exceeded.
Table 13. 1
120
high power
100
80
60
40
20
0
50
60
Figure 13. 2
14

ERROR INFORMATION.

Errors can be divided in three groups:
• Manual reset locking errors (can only be reset by the reset button).
• Blocking errors (will disappear when error is gone)
• Warnings (will disappear when the warning is gone, not stored in the BCU)
The boiler circulator will continue to run during most locking and blocking error codes. This is to prevent the
freezing of the Central Heating circuit when the boiler is in error during the winter period. For some non-volatile
lockouts the circulator will not be running, also see the error tables in this chapter for more details.

Boiler history.

The last 15 lockouts and 15 blocking errors are stored in the boiler control. This boiler history can be shown via the
Boiler History screen via the installer boiler status menu in one of the advanced displays.
Successful ignitions
Failed Ignitions
Flame Failures
Operation days
CH Burner Hours
DHW Burner Hours
86
boiler input control
low power
63
77
70
80
delta T  [°F]
E93.1601EN032.C VGH installation manual
Level
Factory Setting.
3: Factory
63 ºF (35 ºC)
3: Factory
180 Sec.
off
86
90
100
plus 14
°F (+8 °C)).
Range
18....144 ºF (10 ....80 ºC)
1....255 Sec.