Ch With Analog Input Control Of Power Output; Ch Mode 5 - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

12.8.6 CH
WITH ANALOG INPUT CONTROL OF POWER OUTPUT
In this mode of operation, the boiler power (boiler input) is controlled by an analog input signal provided by a
remote means such as a Building Management System or a system controller. The analog input 0-10 VDC is used
to adjust the boiler power output between the minimum boiler input and the maximum boiler input settings.
The minimum analog input signal value will correspond to the minimum modulation rate and the maximum
modulation analog input signal value will correspond to the maximum modulation rate.
All other safety and control functions associated with the boiler will react normally to adverse condition and override
control of the analog signal to prevent an upset condition.
A heat request will be generated by an input of 1.5 volts or higher. The fan speed modulation will occur between
2.0 and 9.0 volts. The request for heat will stop when the voltage drops below 1 volt.
Figure 12. 5
 CH mode 5 will work without sensors.
Parameters
CH_Mode
Table 12. 17
76
Level
2: Installer
E93.1601EN032.C VGH installation manual
; CH
5
MODE
(Default) Value
Settable
0
Mode 0, 1, 2, 3, 4, 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vgh-399-chVgh-500-ch

Table of Contents