Electrical Installation; General; Connection Mains Supply; Electrical Connections - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

11

ELECTRICAL INSTALLATION

General

For operation, the boiler needs a power supply of 120 VAC 60Hz.
The boiler main supply connection is polarity sensitive.
The wiring for the connections can be entered at the bottom of the boiler through the wiring knockouts.
NOTICE: Before starting to work on the boiler, it must be switched off and the power supply to the boiler
must be disconnected.
Electrical wiring must be installed according to all applicable standards and regulations.
In the USA, electrical installation must comply with NFPA 70, National Electrical Code – latest edition,
and with any other national, state, provincial or local codes and regulations.
In Canada, electrical installation must comply with CSA C22.1, Canadian Electrical Code part 1 – latest
edition, and with any other state or local codes and regulations.
Wiring the boiler must only be done by a qualified installer or licensed electrician where required that is
skilled in working on electrical installations and according to all applicable standards.
It is not allowed to change the internal wiring fitted by the manufacturer.
A spare fuse is mounted on the casing of the burner controller.

Connection mains supply

It is advised to use a flexible cable between the cabinet entry (at the bottom) and the connection terminal.
The earth wire has to be longer than the phase and neutral wire.
The power supply cable must be secured by tightening the cable gland at the bottom of the boiler casing.
In case of a flexible cable: use crimp ferrules on each wire end for the terminal connections.
On the high voltage terminal, connect to numbers: 8 = Phase ; 9 = Neutral; PE = Earth.

Electrical connections

Figure 11. 1
Figure 11. 2
NOTICE
High power ignitor
A separate connector for an external igniter is located on the cable tree, near the
boiler controller and labelled "High power ignitor".
The "external ignition transformer" can be ordered, see § 5.1 "Accessories".
This accessory is provided with detailed mounting instructions.
56
LOW VOLTAGE CONNECTIONS
HIGH VOLTAGE CONNECTIONS
Read: "circulator" if the word "pump" is used
E93.1601EN032.C VGH installation manual