Slant/Fin VGH-299-CH Installation And Service Manual page 88

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

Lock
Error
out
code
15
MAX_TEMP_
ERROR
16
FLUE_GAS_
ERROR
17
STACK_ERROR
18
INSTRUCTION_
ERROR
19
ION_CHECK_
FAILED
20
FLAME_OUT_
TOO_LATE
21
FLAME_BEFOR
E_IGNIT
22
TOO_MANY_
FLAME_LOSS
23
CORRUPTED_
ERROR_NR
27
FILLING_TOO_
MUCH
28
FILL_TIME_
ERROR
29
PSM_ERROR
30
REGISTER_
ERROR
32
T_EXCHANGE_
DIFF_ERROR
88
Description
The external overheat
protection is enabled or
the T_Supply sensor
measures a temp. of over
Prot_Overheat_Temp -
SGOverheat_Duplex_Tol
erance for a period of
Max_Value_Period
Flue temperature
exceeded the maximum
flue temperature
Internal software error
Internal software error
Internal software error
Flame still present 10
seconds after closing the
gas valve
Flame is detected before
ignition
Three time flame lost
during 1 demand
Error code RAM byte was
corrupted to an unknown
error code.
Too many automated
filling attempts in a short
time period
Filling takes too long
Internal software error
Internal software error
The 2 exchange sensors
deviate too much for more
than 60 seconds
E93.1601EN032.C VGH installation manual
Cause
Solving
Burner door clixon
Check burnerdoor gasket
tripped because of
and replace burner door
overheating of the
gasket and reset clixon on
burner door or the
burner door or check
water flow is
circulator and waterflow
restricted or back
and replace circulator or
wall thermal fuse has
increase water flow check
tripped because rear
also if valves are closed or
wall insulation disc
check if rearwall fuse is
(combustion
broken if so replace and
chamber) is
also replace rear wall
damaged or broken.
insulation disc (combustion
chamber).
There is no water in
Check if flue sensor is
the heat exchanger
working correctly if not so
or flue gas sensor is
replace flue sensor. Check
malfunctioning or
waterflow if to low increase
heat exchanger is
waterflow.
overheated.
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
wrong earthing of
Check earthing of BCU and
BCU and boiler
boiler
wrong earthing of
Check earthing of BCU and
BCU and boiler
boiler
bad gas supply or
check gas supply pressure,
CO2 level is not
check CO2 level and adjust
correct or bad
if necessary, replace
ignition rod
ignition rod or replace
ignition cable.
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
If output is
Check if there is a leak in
programmed as filing
the central heating system
valve and there are
or if the boiler it self is
to many filing
leaking also check
attempts
expansion vessel on
internal leak
If output is
Check if there is a leak in
programmed as filing
the central heating system
valve and filling takes
or if the boiler it self is
more than 10
leaking also check
minutes
expansion vessel on
internal leak
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
wrongly programmed
reset BCU or replace BCU
BCU or PB
and or display unit
There is not not
Check if the general pump
enough water flow
is running and if all valves
through the heat
are open to make enough
exchanger
flow