Sensor Availability; Ntc Sensor Curve - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

Sensor availability

The following table shows the sensor availability for all CH and DHW control modes. Sensors not mentioned in
the table are optionally available for other functions
0
T_Supply
M
T_Return
O
T_DHW
O
T_Outdoor
---
0-10 Volt
O
Water Flow DHW
O
RT Switch
M
M = Mandatory, O = Optional, --- = Disabled.
Table 11. 3
CH mode 0 – Central Heating demand with thermostat control
CH mode 1 – CH with an outdoor temperature reset and thermostat control
CH mode 2 – Central Heating with full outdoor temperature reset
CH mode 3 – Central Heating with permanent heat demand
CH mode 4 – Central Heating with analog input control of setpoint
CH mode 5 – Central Heating with analog input control of power output
0
T_Supply
O
T_Return
O
T_DHW
---
T_Outdoor
O
0-10 Volt
O
Water Flow DHW
O
RT Switch
O
M = Mandatory, O = Optional, --- = Disabled, N.A. = Not Available.
Table 11. 4
DHW mode 0 – No Domestic Hot Water
DHW mode 1 – Storage with sensor
DHW mode 2 – Storage with thermostat
DHW mode 3 – Instantaneous water heating with plated heat exchanger, flow switch and DHW-out sensor N.A.
DHW mode 4 – Instantaneous water heating with plated heat exchanger and DHW-out sensor
DHW mode 5 to 8 N.A.

NTC sensor curve

All NTC sensors are according to this characteristic: NTC 10K@25°C B3977k
Temperature
Resistance
°C
°F
-30
-22
175203
-25
-13
129289
-20
-4
96360
-15
5
72502
-10
14
55047
-5
23
42158
0
32
32555
5
41
25339
10
50
19873
15
59
15699
Table 11. 5
62
CH Mode
1
2
3
M
M
M
O
O
O
O
O
O
M
M
O
O
O
O
O
O
O
M
M
M
DHW Mode
1
2
3
4
M
M
O
M
O
O
O
M
M
---
M
M
O
O
O
O
O
O
O
O
O
O
O
O
O
M
O
O
Temperature
Resistance
°C
°F
20
68
12488
25
77
10000
30
86
8059
35
95
6535
40
104
5330
45
113
4372
50
122
3605
55
131
2989
60
140
2490
65
149
2084
E93.1601EN032.C VGH installation manual
4
5
M
M
O
O
O
O
O
M
M
O
---
M
---
5 N.A.
6 N.A.
7 N.A.
O
M
M
O
---
O
M
M
---
O
---
---
O
O
O
M
O
M
O
O
O
Temperature
Resistance
°C
°F
70
158
1753
75
167
1481
80
176
1256
85
185
1070
90
194
915
95
203
786
100
212
677
105
221
586
110
230
508
115
239
443
8 N.A.
M
M
M
O
O
M
O
Temperature
Resistance
°C
°F
120
248
387
125
257
339
130
266
298
135
275
262
140
284
232
145
293
206
150
302
183
155
311
163
160
320
145
165
329
130

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vgh-399-chVgh-500-ch

Table of Contents