Flue Temperature Protection; Appliance Selection; Ignition Cycle - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

12.6.3
F
LUE TEMPERATURE PROTECTION
The flue temperature protection function protects against the flue gas reaching a too high temperature.
• When the T_Flue or T_Flue_2 sensor measures above the Max_Flue_Gas_Temp, the control generates a
Flue_Gas_Error.
• When the Flue Switch closes, the control generates a Flue_Gas_Error.
When the control is in a Flue_Gas_Error the fan will run at the minimum fan speed.
Boiler power limitation: All boilers have a flue gas sensor. The control will limit the boiler power when the flue gas
temperature reaches the set Max_Flue_Gas_Temp. The maximum boiler power is linearly limited when the flue
gas temperature is within Max_Flue_Gas_Temp
Parameters are factory set
12.6.4 A
PPLIANCE SELECTION
The control is designed to store specific parameter sets of different boiler models.
By defining specific setting for different appliance models the same control can be used for a complete product
range. Depending on which model the control is applied to, it only will be necessary to change just one single
parameter.
When this parameter is changed the following settings are changed:
• Maximal fan speed
• Minimal fan speed
• Ignition speed*
• Maximum flue gas temperature
*Ignition speed is the same as Pre-Purge Speed and Post Purge speed.
The following appliances are available:
Appliance type 50 - This is the standard mode used for Natural gas
Appliance type 51 - This is the standard mode used for Propane
Appliance type 52 - 55: Not Used

Ignition cycle

During the ignition cycle multiple safety checks are active
False flame detection
Re-ignition
Flame establishing time
Flame out too late
Flame loss
Fan supervision
70
minus 9
If flame is detected at the end of the pre-spark period (Pre-ignite) a lockout error occurs
If at the end of the safety period, no flame is detected the control will go to post-purge to
remove the unburned gas. After this a re-ignition attempt is started following the same cycle.
The number of re-ignition attempts is limited to Max_Ignit_Trials after which a lockout occurs.
Sparking stops in the Flame Proving state to allow for ionization detection. The
Flame Proving state takes Safety_Period - Ignit_Period.
If at the end of the Post purge 0 state the flame is still detected a lockout follows.
When a flame is lost during a burn cycle the control will restart the boiler once. At the second
flame loss the boiler will stop and blocking mode follows. The number of restarts is limited by
the Max_Flame_Trials setting. (Default set to 1)
The fan speed is continuously monitored.
E93.1601EN032.C VGH installation manual
ºF (5 ºC) and Max_Flue_Gas_Temp.