Flexible Polypropylene; Stainless Steel Vent - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

9.4.1
F
LEXIBLE POLYPROPYLENE
For use of flex pipe, it is recommended to have the vent material in 32°F or higher ambient space before bending
at installation. No bends may be made to greater than 45° and ONLY installed in vertical or near vertical
installations.
Insulation is prohibited from use on all types of plastic venting material: PVC, CPVC, and
Polypropylene.
Use only the adapters and vent system listed.
DANGER
DO NOT mix vent systems of different types or manufacturers.
Failure to comply could result in severe personal injury, death, or substantial property damage.
All vent connections MUST be secured by the vent manufacturer's joint connector.
The installer must use a specific vent starter adapter at the flue collar connection. The adapter
is supplied by the vent manufacturer to adapt to its vent system.
Installations must comply with applicable national, state, and local codes.
NOTICE
For Canadian installation, polypropylene vent must be listed as a ULC-S636 approved system.
Installation of a polypropylene vent system must adhere to the vent manufacturer's installation
instructions supplied with the vent system.
9.4.2
S
TAINLESS STEEL VENT
This product has been approved for use with stainless steel using the manufacturers listed.
Approved stainless steel vent pipe and fittings.
SUPPLIER
TYPE
Duravent
FasNSeal, FasNSeal Flex
Security Chimneys
Secure Seal SS/SSD/SSID
Heat Fab
Saf-T EZ Seal
Table 9-11
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking
precaution to ensure no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially
designed adapters and sealing method, see manufacturer's instructions.
Use only the materials, vent systems, and terminations listed.
DO NOT mix vent systems of different types or manufacturers. Failure to comply could result
in severe personal injury, death, or substantial property damage.
WARNING
The installer must use a specific vent starter adapter at the flue collar connection, supplied
by the vent manufacturer to adapt to its vent system.
Installations must comply with applicable national, state, and local codes. Stainless steel
vent systems must be listed as a UL-1738 approved system for the United States and a
NOTICE
ULC-S636 approved system for Canada.
Installation of a stainless-steel vent system must adhere to the stainless-steel vent
manufacturer's installation instructions supplied with the vent system.
Approved Stainless Steel Terminations.
Duravent
FasNSeal
BOILER
TERMINATION
VGH 299
FSBS4 (bird screen wall)
VGH 399
FSRC4 (rain cap roof)
FSBS6 (bird screen wall)
VGH 500
FSRC6 (rain cap roof)
Table 9-12
.
Security Chimneys
Secure Seal
TERMINATION
SS4STAU (screen termination
SS4RC (rain cap roof)
SS6STAU (screen termination
SS6RC (rain cap roof)
E93.1601EN032.C VGH installation manual
HeatFab
Saf-T EZ Seal/ EZ 316
TERMINATION
5490CI (horizontal termination)
5400CI (rain cap)
5690CI (horizontal termination)
5600CI (rain cap)
37