General

The boiler controller is designed to function as a standalone control unit for intermittent operation on heating
appliances with a premix (modulating) burner and a pneumatic air-gas system.
Flame establishing period
Safety time
Ignition attempts
Pre-purge time
Pre-ignition time
Flame failure response time
Flame-current
Cable length AL-BUS
This concerns the total length of the cable, not the length between two boilers. The length differs with the diameter of the cable.
1)
Table 11.5
C
IRCULATOR START EXERCISE EVERY
To protect the circulator from getting stuck at a certain position it is forced to run for 10 seconds every 24 hours.
This is done only for the boiler loop circulator at the start-up of the board.
F
ROST PROTECTION
The Frost protection function protects the boiler and boiler loop from freezing.
The T_Supply, T_Supply_2 and T_Return sensors are checked for generating a Frost protection demand.
When any of the sensors drop below FP_Start_Circulator the boiler loop circulator is switched ON for CH.
When any of the sensors drop below FP_Start_Burn the boiler is fired.
When all of the sensors measure above FP_Stop the Frost protection demand is ended.
When the demand for Frost protection is ended the circulators will post-circulate for CH_Post_Circulator_Period.
Parameters are factory set
F
LUE TEMPERATURE PROTECTION
The flue temperature protection function protects against the flue gas reaching a too high temperature.
When the T_Flue or T_Flue_2 sensor measures above the Max_Flue_Gas_Temp, the control generates a
Flue_Gas_Error.
When the Flue Switch closes, the control generates a Flue_Gas_Error.
When the control is in a Flue_Gas_Error the fan will run at the minimum fan speed.
Boiler power limitation
All boilers have a flue gas sensor. The control will limit the boiler power when the flue gas temperature reaches
the set Max_Flue_Gas_Temp. The maximum boiler power is linearly limited when the flue gas temperature is
within Max_Flue_Gas_Temp minus 9 ºF (5 ºC) and Max_Flue_Gas_Temp.
Parameters are factory set.
Mains input
Minimum
Start-detection
1
24
E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
1 x 5AT, 120V
2 seconds
5 seconds
5
≥ 2...60 seconds (not safety critical)
2 seconds (not safety critical)
< 1.0 second
1.0 μA
1.5 μA
AWG (mm
HOURS
2
)
Cable length (m)
23
(0.25)
328.1 ft (100)
20
(0.5)
656.2 ft (200)
18
(0.75)
984.3 ft (300)
17
(1.0)
1312.3 ft ( 400)
15
(1.5)
1968.5 ft (600)