Slant/Fin VGH-299-CH Installation And Service Manual page 91

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

Lockout
Error
code
116
LOW_WATER_P
RESSURE_SEN
SOR
118
WD_COMM_ER
ROR
119
RETURN_OPEN
120
SUPPLY_OPEN
122
DHW_OPEN
123
FLUE_OPEN
125
OUTDOOR_OP
EN
126
RETURN_SHOR
TED
127
SUPPLY_SHOR
TED
129
DHW_SHORTE
D
130
FLUE_SHORTE
D
132
OUTDOOR_
SHORTED
133
NET_FREQ_ER
ROR
134
RESET_BUTTO
N_ ERROR
135
PHASE_NEUTR
AL_ REVERSED
136
T_EXCHANGE_
BLOCK_ERROR
Description
Low water pressure,
generated when the
pressure drops below
Minimal_Pressure, or when
the pressure drops below
4.5 PSI .
Watchdog communication
error
Return sensor open
Supply sensor open
DHW sensor open
Flue sensor open
Outdoor sensor open
Return sensor shorted
Supply sensor shorted
DHW sensor shorted
Flue sensor shorted
Outdoor sensor shorted
Net freq. error detected by
the watchdog
Too many resets in a short
time period
Live and neutral of the
main voltage power supply
input are reversed
Exchange temperature
exceeded 194 ºF (90 ºC).
E93.1601EN032.C VGH installation manual
Cause
Solving
Not enough water
Fill up the system and
pressure
check if there are any
water leakages
wrong
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
malfunctioning
check connection to BCU
return sensor or
or check resistance NTC
not connected
sensor
malfunctioning
check connection to BCU
supply sensor or
or check resistance NTC
not connected
sensor
malfunctioning
check connection to BCU
DHW sensor or
or check resistance NTC
not connected
sensor
malfunctioning flue
check connection to BCU
sensor or not
or check resistance NTC
connected
sensor
malfunctioning
check connection to BCU
outdoor sensor or
or check resistance NTC
not connected or
sensor or change CH-
wrong CH-mode
mode
programmed
malfunctioning
check connection to BCU
return sensor or
or check resistance NTC
short circuiting
sensor
malfunctioning
check connection to BCU
supply sensor or
or check resistance NTC
short circuiting
sensor
malfunctioning
check connection to BCU
DHW sensor or
or check resistance NTC
short circuiting
sensor
malfunctioning
check connection to BCU
Flue sensor or
or check resistance NTC
short circuiting
sensor
malfunctioning
check connection to BCU
Outdoor sensor or
or check resistance NTC
short circuiting
sensor
Wrong frequency
Check frequency on the
from power grid or
mains of the boiler (60Hz)
aggregate
Reset many times
wait or disconnect and
by user or installer
reconnect power supply
Fase and neutral
Change fase and neutral
are wrongly
connected
water temperature
Check
is above 194 ºF
functioning. Check/open all
(90 ºC).
valves that might restrict
water flow through the unit.
Check
circulator(s) that influences
flow
Check
resistance
spare capacity of the unit
circulator.
circulator
external
system
through
the
unit.
if
the
system
exceeds
the
91