Blocking Codes - Slant/Fin VGH-299-CH Installation And Service Manual

High efficiency condensing gas boiler
Hide thumbs Also See for VGH-299-CH:
Table of Contents

Advertisement

Blocking codes

Lockout
Error
code
100
WD_ERROR_R
AM
101
WD_ERROR_R
OM
102
WD_ERROR_ST
ACK
103
WD_ERROR_
REGISTER
104
WD_ERROR_X
RL
105
HIGH_TEMP_E
RROR
106
REFHI_TOO_HI
GH
107
REFHI_TOO_LO
W
108
REFLO_TOO_HI
GH
109
REFLO_TOO_L
OW
110
REFHI2_TOO_H
IGH
111
REFHI2_TOO_L
OW
112
REFLO2_TOO_
HIGH
113
REFLO2_TOO_
LOW
114
FALSE_FLAME
90
Description
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
T_Supply sensor measures
over Stay_Burning_Temp
for a period of
Max_Value_Period.
Internal hardware error
Internal hardware error
Internal hardware error
Internal hardware error
Internal hardware error
Internal hardware error
Internal hardware error
Internal hardware error
Flame is detected in a state
in which no flame is
allowed to be seen
E93.1601EN032.C VGH installation manual
Cause
Solving
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
not enough
Check functioning of the
waterflow over
circulator.
heat exchanger
Check/open all valves that
might restrict the water
flow through the unit.
Check for an external
system circulator that
influences flow through
the unit.
Check if the system
resistance exceeds the
spare capacity of the unit
circulator.
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrongly
reset BCU or replace BCU
programmed BCU
and or display unit
or PB
wrong earthing of
Check earthing of BCU
BCU and boiler
and boiler

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vgh-399-chVgh-500-ch

Table of Contents