Slant/Fin CB-45 Installation And Operating Instructions Manual

Concept 21 series cast-iron hot water boilers gas fired sealed combustion direct vent, category i, or category iv venting flexibility

Advertisement

CONCEPT 21
• Cast-iron • Hot water boilers • Gas Fired • Sealed Combustion
• Direct Vent, Category I, or Category IV Venting Flexibility
INSTALLATION AND OPERATING INSTRUCTIONS
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Specifications and Dimensions . . . . . . . . . . . . . . . . . . . . . . . .2
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Approved Venting Applications . . . . . . . . . . . . . . . . . . . . 4
Direct Vent Application Requirements . . . . . . . . . . . . . 4-8
Category IV Venting Requirements . . . . . . . . . . . . . 9-11
Category I Venting Requirements . . . . . . . . . . . . . 12-14
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
Operation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-19
Input Rate Adjustment Specifications . . . . . . . . . . . . . . . . . .20
Testing of System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Sequence of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-27
Air and Gas Orifices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-29
Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Maintenance Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Boiler Package/Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Heating Contractor
Address
Phone Number
®
Models CB-45 through CB-180
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS
AND STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
LIQUEFIED PETROLEUM (L.P .)
PROPANE FIRED GAS BOILERS
Installation location ONLY as permitted in paragraph entitled
"LIQUEFIED PETROLEUM (L.P .) PROPANE GAS FIRED
BOILER LOCATION" on page 3 of this instruction book.
The above warning does not apply to NATURAL gas fired
boilers.
NOTICE: INSTALLATION AND SERVICE MUST BE PERFORMED BY A
TRAINED AND QUALIFIED TECHNICIAN.
The installation must conform to the requirements of the
National Fuel Gas Code ANSI Z223.1 or the CSA B149.1-00
for natural gas and propane and the requirements of the
authority having jurisdiction as well as the requirements in
this instruction manual. In addition, where required by the
authority having jurisdiction, installation must conform to the
Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1 or the CSA B149.1-00 for
natural gas and propane. If there is any conflict in the above
requirements, then the more stringent requirement will apply.
WARNING
This boiler, gas piping and accessories must be installed,
connected, serviced and repaired by a trained, experienced
service technician, familiar with all precautions required for
gas fired equipment and licensed or otherwise qualified, in
compliance with the authority having jurisdiction.
This manual must be left with owner, hung on or
adjacent to the boiler. Owner should retain manual
for future reference.
Boiler Model Number
Boiler Serial Number
Installation Date
Printed in Canada
Publication No. CB-40 Rev. C
Part No. 66-1001

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin CB-45

  • Page 1: Table Of Contents

    ® CONCEPT 21 Models CB-45 through CB-180 • Cast-iron • Hot water boilers • Gas Fired • Sealed Combustion • Direct Vent, Category I, or Category IV Venting Flexibility INSTALLATION AND OPERATING INSTRUCTIONS Contents ........Page...
  • Page 2 32mm (1 1/4") CIRC. PUMP GAS SUPPLY 13mm (1/2") NPT LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW DIMENSIONS INCHES Boiler Model CB-45 743 29.25 794 31.25 527 20.75 CB-90 743 29.25 794 31.25 527 20.75 CB-135 743 29.25 794 31.25 527 20.75...
  • Page 3: Installation Requirements

    INSTALLATION REQUIREMENTS or similar location where heavier-than-air-gas might NOTICE: INSTALLATION AND SERVICE MUST BE collect. Appliances so fueled shall not be installed in PERFORMED BY A QUALIFIED HEATING CONTRACTOR an above-grade under-floor space or basement The installation must conform to the requirements of unless such location is provided with an approved the National Fuel Gas Code ANSI Z223.1 and CSA means for removal of unburned gas.”...
  • Page 4: Approved Venting Applications

    The vent piping minimum and maximum equivalent vent length for each may be run horizontally or vertically to the outdoors, to a model of boiler. Refer to Slant/Fin Parts List, Publication common terminal with the combustion air intake or CB 10PL.
  • Page 5 TO PREVENT FLUE GAS DISCHARGE INTO SPACE. DIRECT VENT APPLICATION REQUIREMENTS Periodic inspection should be made of this assembly for deterioration of the tubing and to insure that the trap is AIR INTAKE filled with water, but not plugged. If it is plugged or A.
  • Page 6 Figure 5b. Vent terminal installation All Concept 21 boiler models are certified for horizontal Direct Venting utilizing the vent terminal provided by Slant/Fin only. This vent terminal must be mounted on a vertical wall outside surface. Terminal CANNOT be mounted on a roof or any horizontal surface.
  • Page 7 DIRECT VENTING WITHOUT VENT TERMINAL Figure 7a. Vent and air intake run through a pitched roof EXHAUST WITH SCREEN Vertical Venting Configurations 3048mm (10 ft) All Concept 21 boiler models are certified for vertical or less AIR INTAKE 180° ELBOW Direct Venting utilizing the following configurations.
  • Page 8 DIRECT VENTING WITHOUT VENT TERMINAL Figure 8a. Vent run through a roof and air intake run through a wall Vertical Venting Configurations REFER TO VENT PIPE EXHAUST WITH SCREEN REQUIREMENTS SHOWN IN 2. Vent piping vertically run up through a roof and air PREVIOUS FIGURES FOR intake horizontally run out a vertical wall.
  • Page 9: Category Iv Venting Requirements

    Length* Elbows Model Elbows* Protect against closure of openings by snow and debris. Elbows* Inspect frequently. CB-45 30 100 1524 5 No mechanical draft exhaust or supply fans are to be used in CB-90 30 100 1524 5 or near the boiler area.
  • Page 10 Category IV Venting Requirements B. When joining the various components of the above E. The vertical portion of the pipe must be supported in at leas listed vent systems, the manufacturers’ instructions one location for each 9m (30 feet) of vertical run. A firestop should be closely followed to insure proper sealing.
  • Page 11 Figure 11. Vertical Category IV Venting through a roof Figure 12. Vertical Category IV Venting up an existing chimney ROOF LINE VENT TERMINATION WITH VENT TERMINATION WITH 3048mm 3048mm SCREEN SCREEN (10 FT.) (10 FT.) OR LESS OR LESS 305mm (1 FT.) MIN. 610mm (2 FT.) MIN.
  • Page 12: Category I Venting Requirements

    For a masonry vitreous tile-lined chimney which is not exposed to the outdoors, use Table 1 in this Slant/Fin Provisions for combustion and ventilation air must be made manual for venting requirements. DO NOT install this in accordance with section 5.3, Air for Combustion and...
  • Page 13 Natural Draft Chimney and Type “B” Venting Diagrams Figure 13. Chimney Venting for models specified in Table 1 only. Minimum vent connectors diameter is 127mm (5 inches). It may have to be upsized to 152mm or 178mm (6 or 7 inches) [see Table 1].
  • Page 14 Natural Draft Chimney and Type “B” Venting Tables Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined) Chimneys not exposed to the outdoors below the roof line. (127mm [5"] dia. vent adapter must be used) Concept Additional CSA B149.1-00 Boiler Gas Appliance for natural gas Model(s) †...
  • Page 15: Water Piping

    Figure 15. Water piping Note: Orientation of piping drawn for clarity. Observe relative location of components. WATER PIPING FILL AND PURGE HEATING SYSTEM Always follow good piping practices. Observe minimum • Make sure flow direction arrows on components are 25mm (1") clearance to combustibles around all facing in direction of flow.
  • Page 16: Gas Piping

    piping system by closing its individual manual shutoff GAS PIPING valve during any pressure testing of the gas supply A. Local installation codes apply. The pipe joint piping system at test pressures equal to or less than compound used on threads must be resistant to the 3.5 kPa (1/2 PSIG).
  • Page 17 Figure 17. Power and thermostat wiring Power Connections • Remove electrical junction box cover. • HOT CONNECTION LEAD IS BLACK. • NEUTRAL CONNECTION LEAD IS WHITE. • Connect ground inside box. DO NOT REVERSE POWER CONNECTIONS: if reversed, ignition control will not detect a flame and will go into safety shutdown.
  • Page 18: Operation Procedures

    4. Remove cap on burner enclosure pressure fitting and recommended. connect to low side of gauge tubing. Available from Slant/Fin is a calibration gauge kit (part 5. Turn power on. Raise thermostat to start boiler. number 665185) that has a gauge mounted on a stand 6.
  • Page 19 STEP B: CALIBRATE GAS VALVE 6. Locate the knurled adjustment knob on side of air filter Note: This step will set the air/gas ratio for optimum box. See figure 20. combustion. The purpose of this step is NOT to set input 7.
  • Page 20: Input Rate Adjustment Specifications

    Chart 1: Input Rate Adjustment Specifications for Direct Vent and Category IV Installations Air Flow Boiler Model and Allowable Input * Percent of change Differential to nominal boiler Pressure † CB-45 CB-90 CB-135 CB-180 input rate BTUH BTUH BTUH BTUH mm w.c.
  • Page 21: Testing Of System

    Testing of System NORMAL SYSTEM STARTUP TEST COMMON VENTING SYSTEM (IF REQUIRED) Follow lighting instructions on page 30. Safe lighting and If existing boiler was removed from a common venting other performance criteria were met with the gas manifold system, common venting system may be too large for and control assembly provided on the boiler when the proper venting of appliances remaining connected to it.
  • Page 22: Sequence Of Operations

    SEQUENCE OF OPERATION THERMOSTAT CALLS FOR HEAT DISPLAY LED CIRCULATOR ON INDICATION DISPLAY FAULT AND CLOSE FAULT CONTACTS HIGH HIGH LIMIT CIRCULATOR LIMIT OPEN OVER CONTINUES TO RUN CLOSED? 1 HOUR? DISPLAY FAULT AND CLOSE PRESSURE CIRCULATOR FAULT CONTACTOR. WAIT FOR SWITCH CONTINUES TO RUN.
  • Page 23: Wiring Diagrams

    WIRING DIAGRAMS...
  • Page 24: Troubleshooting

    TROUBLESHOOTING Boiler Failure Codes Indicator codes and component location Indicator Fault indicated Page Steady ON Control internal failure DIAGNOSTIC INDICATOR LIGHT (RED) 1 Flash High limit open Carefully note red diagnostic indicator light. When a 2 Flashes No ignition system failure occurs, indicator light will show a series of 3 Flashes Pressure switch problem quick flashes with a short interval between the series of...
  • Page 25 Operation Procedures on page 19 Orifice sizing is Check gas and air orifice size and gas type. Orifice plate is If size not correct, contact Slant/Fin not correct? stamped with model number and gas type. Refer to orifice Technical Services Dept.
  • Page 26 Refer to Replacement Parts information on TROUBLESHOOTING: POSSIBLE CAUSES AND SOLUTIONS page 31 when parts need to be replaced. DIAGNOSTIC “3 FLASHES” - PRESSURE SWITCH PROBLEM Important Note: Boiler control checks for switch contacts to be open before combustion blower is turned on and switch contacts to be closed once blower is running and proper air flow is established.
  • Page 27 TROUBLESHOOTING PROCEDURES • Disconnect wires to gas valve. May be necessary to Note: All of the procedures below require the removal disconnect gas supply line to gas valve to move of some of the boiler jacket panels. assembly slightly. • Disconnect air adapter from burner enclosure. Checking flame sensing current •...
  • Page 28: Air And Gas Orifices

    Combination Air and Gas Orifice Plate Figure 23. Combination Air and Gas Orifice Plate Installation Note: This original design of the air and gas orifice holes stamped into the same plate has been revised on the Concept boiler. Whether this design is implemented on any particular Concept boiler depends on when the boiler was manufactured.
  • Page 29 Air and Gas Orifice Plates with Convertible Gas Orifice Figure 24. Convertible Gas Orifice Installation Note: This revised design features a gas orifice plate which contains both the natural gas and the propane gas orifice hole. Whether this design is implemented on any particular Concept boiler depends on when the boiler was manufactured.
  • Page 30: Lighting Instructions

    LIGHTING INSTRUCTIONS (Reference For Labels 65-0640 & 65-0645) • Immediately call your gas supplier from a neighbor's FOR YOUR SAFETY READ BEFORE OPERATING phone. Follow the gas supplier's instructions. WARNING: If you do not follow these instructions exactly, a • If you cannot reach your gas supplier, call the fire fire or explosion may result causing property damage, department.
  • Page 31: Maintenance Procedures

    Replace (recommended) or clean filter annually (more of the boiler and is especially recommended in areas often if conditions dictate). Slant/Fin replacement air filter, where water quality is a problem. A reputable water part number 66-0515 must be used. Can be cleaned with treatment company should be consulted for determining soap and water;...
  • Page 32: Boiler Package/Options

    • Horizontal venting with separate vent and air intake • Chimney or “B” vent venting ©Slant/Fin Corp. 1998. Printed in Canada 0501. Publication No. CB-40 Rev. C. SLANT/FIN LTD/LTEE, 6450 Northam Drive, Mississauga, Ontario L4V 1H9 • Phone: (905) 677-8400 / FAX: (905) 677-1829 e-mail: slantcan@aol.com...

This manual is also suitable for:

Cb-90Cb-135Cb-180Concept 21 cb-180