Functions of each part
(1)Operation monitor LEDs ..
(2)Station number selector
switches (Rotary switches)
(3)Mode selector switches ......
(4)RS485 interface ......
(5)Input terminals, Output terminals ...
(6)Power supply terminal.............
(7)I/O monitor LEDs .................
(8)Expansion connector.......
For the information on the specifications and connections of hte I/O terminals and
power supply terminal, refer to the next page.
Indicates communication status and operation mode.
Set the station number of the MEWNET-F.Point the arrow to the
number to be used. (Set tens place and ones place separately.)
Setting range: 01 to 32
* When setting numbers exceeding the range, the setup error occurs
(ALARM LED flashes), and communication becomes impossible.
* The settings will be accepted when the power turns on.
Sets the terminal station and the output mode a communication
error occurs.
SW
Setting
1、2
Terminal station setting
Output condition during
3
a communication error
* The settings of SW1 and SW2 should be the same.
* The swithces are all set to the OFF position at the factory.SW4 is
not used.
* The settings will be accepted when the power turns on.
For connecting the communication cables.
They are configured with 8-point input/output terminals
or 16-point input/output terminals.
Supply the power to activate the I/O terminal board.
Lights up when input or output is ON.Lights off when input
or outout is OFF.
Connects the primary I/O terminal unit and the expansion I/O
terminal unit with a cable.
Use a PL Mark expansion cable (APL2510, APL2511 or APL2515).
OFF
Not terminal
Terminal station
station
Maintains its
Output off
output condition
ON