3 Error Tables
Event code
Event name
54011409 hex
That File Name
Already Exists
5401140A hex
Write Access
Denied
5401140B hex
Too Many Files
Open
5401140C hex
Directory Does Not
Exist
5401140D hex
File or Directory
Name Is Too Long
5401140E hex
SD Memory Card
Access Failed
54011800 hex
EtherCAT Commu-
nications Error
54011801 hex
EtherCAT Slave
Does Not Respond
54011802 hex
EtherCAT Timeout
54011803 hex
Reception Buffer
Overflow
54011804 hex
SDO Abort Error
54011805 hex
Saving Packet
Monitor File
54011806 hex
Packet Monitoring
Function Not
Started
3-20
Meaning
An instruction could not be
• A file already exists
executed because the file
name specified for the
instruction already exists.
An attempt was made to
• The file or directory
write to a write-protected
file or directory when an
instruction was executed.
The maximum number of
• The maximum number
open files was exceeded
when opening a file for an
instruction.
The directory specified for
• The directory speci-
an instruction does not
exist.
The file name or directory
• The file name or direc-
name that was specified for
an instruction is too long.
SD Memory Card access
• The SD Memory Card
failed.
• The SD Memory Card
Accessing the EtherCAT
• The EtherCAT network
network failed when an
instruction was executed.
Accessing the target slave
• The target slave does
failed when an instruction
was executed.
• The target slave is not
A timeout occurred while
• Communications with
trying to access an Ether-
CAT slave when an instruc-
tion was executed.
The receive data from an
• The receive data from
EtherCAT slave overflowed
the receive buffer when an
instruction was executed.
An SDO abort error was
• Depends on the speci-
received from an EtherCAT
slave when an instruction
was executed.
An instruction for packet
• An instruction for
monitoring was executed
while saving an EtherCAT
packet monitor file.
A Stop EtherCAT Packet
• A Stop EtherCAT
Monitor instruction was
executed when EtherCAT
packet monitoring was
stopped.
Assumed cause
Maj
Prt
with the same name
as the name specified
for the instruction to
create.
specified for the
instruction to write is
write-protected.
of open files was
exceeded when open-
ing a file for an instruc-
tion.
fied for an instruction
does not exist.
tory name that was
specified for the
instruction to create is
too long.
is broken.
slot is broken.
is not in a usable sta-
tus.
not exist.
in an operating condi-
tion.
the target slave timed
out.
the slave overflowed
the receive buffer.
fications of the slave.
packet monitoring was
executed while saving
an EtherCAT packet
monitor file.
Packet Monitor
instruction was exe-
cuted when EtherCAT
packet monitoring was
stopped.
NJ-series Troubleshooting Manual (W503)
Level
Refer-
ence
Min
Obs
Info
S
NJ-series
Instruc-
tions Ref-
erence
Manual
(Cat. No.
W502)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.