The following table lists the events that can occur for an EtherNet/IP Unit with the following model num-
ber.
CJ1W-EIP21
Event code
Event name
047A0000 hex
Unit Memory
Error (Device
Error)
047B0000 hex
Non-volatile
Memory
Error
047C0000 hex
Communica-
tions Control-
ler Error
14840000 hex
Invalid Com-
munications
Parameter
14850000 hex
Tag Data-
base Error
34A80000 hex
Verification
Error
34A90000 hex
Tag Data Link
Error
34AA0000 hex
Tag Refresh
Error
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An error occurred
• There is a source of noise
when writing to the
nearby.
error history or
• Non-volatile memory failure
device parameters
in non-volatile
memory in the Eth-
erNet/IP Unit.
An error occurred in
• There is a source of noise
non-volatile mem-
nearby.
ory.
• Non-volatile memory failure
An error occurred in
• Noise
the communica-
• Communications Controller
tions controller.
hardware error
An error was found
• The power was interrupted dur-
in the validation
ing a download.
check of the param-
• A communications error
eters for tag data
occurred during a download.
links that are saved
• Non-volatile memory failure
in non-volatile
memory.
A tag database
• The power was interrupted dur-
error occurred in
ing a download.
the CPU Unit when
• A communications error
using variables for
occurred during a download.
tag data links, sta-
tus layout, etc.
The information
• The specified target does not
registered for a tar-
exist.
get node in the tag
• Variable names do not match.
data link parame-
• The connection size is incor-
ters is different from
rect.
the actual node
• Insufficient connection
information.
resources
There were two or
• The power supply to the target
more errors in a
node is OFF.
connection as an
• Communications with the target
originator. The fol-
node stop.
lowing are
• The Ethernet cable for Ether-
excluded.
Net/IP is disconnected.
• Connections as a
• The Ethernet cable for Ether-
target
Net/IP is disconnected.
• Connection time-
• Noise
outs due to a Link
OFF Error with
the Ethernet
switch
An unsupported
• An unsupported data area or
data area or
address range was specified for
address range is
the tag data links.
specified for the tag
data links.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
CJ-series Eth-
erNet/IP Units
Operation
Manual for NJ-
series CPU
Unit (Cat. No.
W495)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
Reference