Omron NJ Series Troubleshooting Manual page 168

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
35230000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established,
Incorrect
FSoE Slave
Address
Error
35240000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established,
Incorrect
Frame Error
65200000 hex
I/O Power
Supply Volt-
age Error
65210000 hex
Output Power
Interrupt Cir-
cuit Error
65220000 hex
External Test
Signal Failure
at Safety
Input
65230000 hex
Discrepancy
Error at
Safety Input
65240000 hex
Overload
Detected at
Test Output
65250000 hex
Stuck-at-high
Detected at
Test Output
65270000 hex
Short Circuit
Detected at
Safety Output
3-106
Meaning
Assumed cause
Safety process data
• The setting of the FSoE slave
communications
address in the safety process
was not estab-
data communications settings
lished with the
is different from the setting in
Safety CPU Unit
the Unit.
because of an
incorrect FSoE
slave address.
Safety process data
• An incorrect frame was
communications
received in safety process data
was not estab-
communications. There is
lished with the
excessive noise.
Safety CPU Unit
because an incor-
rect frame was
received.
An incorrect I/O
• The input power or output
power supply volt-
power is not supplied correctly.
age was detected.
An error was
• The wiring is not correct or
detected by the out-
there is a fault in the hardware.
put power interrup-
tion test.
An error was
• The positive power supply wire
detected in test
is in contact with the input sig-
pulse evaluation of
nal line.
the safety input ter-
• The input signal lines are
minals.
shorted.
• The external device is faulty.
An error was
• There is a ground fault or dis-
detected in discrep-
connection in the input signal
ancy evaluation of
line.
safety input termi-
• The connected device is faulty.
nals.
• The setting of the discrepancy
time is not correct.
• Chattering occurred in the input
signal from the external input
device, such as a safety door.
An overcurrent was
• There is a ground fault on the
detected at the test
output signal line.
output terminal.
• The external device is faulty.
It was detected that
• The positive power supply line
the test output ter-
is in contact with the output sig-
minal is stuck ON.
nal line.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software error
or excessive noise.
A ground fault was
• There is a ground fault on the
detected on the
output signal line.
safety output termi-
nal.
Level
Maj
Prt
Min
Obs Info
S
NX-series
Safety Control
Unit User's
Manual (Z930)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)