Event code
Event name
04A80000 hex
Control
Power Sup-
ply Under-
voltage
04A90000 hex
Overvoltage
04AA0000 hex
Main Circuit
Power Sup-
ply Under-
voltage
(Undervolt-
age between
positive and
negative ter-
minals)
04AB0000 hex
Main Circuit
Power Sup-
ply Under-
voltage (AC
Cutoff
Detected)
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The voltage
• Power supply undervoltage. Or,
between the posi-
the power supply voltage
tive and negative
dropped because there was
terminals in the
inrush current when the main
control power sup-
power supply was turned ON.
ply converter
• A momentary power interrup-
dropped below the
tion occurred.
specified value.
• The Servo Drive failed.
The power supply
• The voltage between the posi-
voltage exceeded
tive and negative terminals in
the allowable input
the control power supply con-
voltage range.
verter exceeded the specified
value.
• The voltage was suddenly
increased by the phase
advance capacitor or the unin-
terruptible power supply (UPS).
• The Regeneration Resistor wir-
ing is broken.
• The External Regeneration
Resistor is not suitable.
• The Servo Drive failed.
If the Undervoltage
• Insufficient power supply
Error Selection
capacity
(3508 hex) is set to
• The electromagnetic contactor
1, a momentary
in the main circuit power supply
power interruption
was tripped.
occurred between
• A momentary power interrup-
L1 and L3 for longer
tion occurred.
than the value
• A Servo Drive with 3-phase
specified for the
input specifications was oper-
Momentary Hold
ated with a single-phase power
Time. The voltage
supply.
between the posi-
• The Servo Drive failed.
tive and negative
terminals in the
main power supply
converter dropped
below the specified
value while the
Servo was ON.
If the Undervoltage
• Insufficient power supply
Error Selection
capacity
(3508 hex) is set to
• The electromagnetic contactor
1, a momentary
in the main circuit power supply
power interruption
was tripped.
occurred between
• A momentary power interrup-
L1 and L3 for longer
tion occurred.
than the value
• A Servo Drive with 3-phase
specified for the
input specifications was oper-
Momentary Hold
ated with a single-phase power
Time. The voltage
supply.
between the posi-
• The Servo Drive failed.
tive and negative
terminals in the
main power supply
converter dropped
below the specified
value while the
Servo was ON.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
Cylinder-type
Motor Manual
(Cat. No. I576)
and Linear
Motor Manual
(Cat. No. I577)
S
Same as
above.
S
Same as
above.
S
Same as
above.
Reference
3
3-109