3 Error Tables
Event code
Event name
74930000 hex
TIMING input
error
74940000 hex
RESET input
error
74950000 hex
ZERO input
error
74960000 hex
ZEROCLR
input error
3-128
Meaning
Assumed cause
TIMING input pro-
• TIMINGx input turned ON in the
cessing was not
FUN mode.
executed correctly.
• TIMINGx input turned ON or
OFF while RESETx input was
ON.
• TIMINGx input turned ON in a
non-measurement state.
• TIMINGx input turned ON
before the "delay time + sam-
pling time" elapsed.
RESET input pro-
• RESETx input turned ON in the
cessing was not
FUN mode.
executed correctly.
ZERO input pro-
• ZEROx input turned ON in the
cessing was not
FUN mode.
executed correctly.
• ZEROx input turned ON in a
non-measurement state.
• ZEROx input turned ON for a
task whose status is OFF.
ZEROCLR input
• ZEROCLRx input turned ON in
processing was not
the FUN mode.
executed correctly.
Level
Maj
Prt
Min
Obs Info
S
ZW-CE1@T
Confocal Fiber
Type Displace-
ment Sensor
User's Manual
(Cat. No.
Z332)
S
Same as
above.
S
Same as
above.
Same as
S
above.