Event code
Event name
34240000 hex
FTP Server
Setting Error
34250000 hex
NTP Client
Setting Error
34260000 hex
SNMP Set-
ting Error
34270000 hex
Tag Name
Resolution
Error
50010000 hex
Controller
(Ver. 1.02)
Insufficient
Memory
Warning
84030000 hex
DNS Server
Connection
Error
84040000 hex
NTP Server
Connection
Error
84070000 hex
Tag Data Link
Connection
Failed
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An error was
• Setting error
detected in the FTP
• Power was interrupted when a
server settings.
download was in progress for
the FTP server settings.
• Memory error
An error was
• Setting error
detected in the NTP
• Power was interrupted when a
client settings.
download was in progress for
the NTP client settings.
• Memory error
An error was
• Setting error
detected in the
• Power was interrupted when a
SNMP agent/trap
download was in progress for
settings.
the SNMP agent/trap settings.
• Memory error
Resolution of a tag
• The size of the network-pub-
used in a tag data
lished variable is different from
link failed.
the tag settings.
• The I/O direction set for a tag
data link and the I/O direction of
the Controller variable do not
match.
• There are no network-published
variables for the Controller tag
settings.
• A variable in the Controller that
is set for a tag data link has the
Network Publish attribute set to
Input but also has the Constant
attribute.
The amount of data
• The amount of data for the
for the EtherCAT
EtherCAT slave configuration,
slave configuration,
network-published information,
network-published
or other data exceeds the value
information, or
that is specified for the CPU
other data exceeds
Unit.
the value that is
specified for the
CPU Unit. You may
not be able to per-
form online editing
or other operations.
Connection with the
• Parameter error
DNS server failed.
• Server is down.
• An error occurred in the com-
munications path.
Connection with the
• Parameter error
NTP server failed.
• Server is down.
• An error occurred in the com-
munications path.
Establishing a tag
• The tag data link connection
data link connection
information is not the same for
failed.
the originator and target.
• Insufficient connections
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
NJ-series
CPU Unit
Built-in Ether-
Net/IP Port
User's Manual
(Cat. No.
W506)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
Reference