Omron NJ Series Troubleshooting Manual page 159

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Event code
Event name
64FD 0000 hex
Unit Under
Range for
Channel 6
64FE0000 hex
Unit Under
Range for
Channel 7
64FF 0000 hex
Unit Under
Range for
Channel 8
90400000 hex
Event Log
Cleared
 Temperature Input Units
Event code
Event name
00200000 hex
Non-volatile
Memory
Hardware
Error
05100000 hex
A/D Con-
verter Error
05110000 hex
Cold Junction
Sensor Error
10410000 hex
Control
Parameter
Error in Mas-
ter
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The analog input
• The analog input data went
data for input chan-
below the lower limit of the input
nel 6 went below
range. Or, the analog output
the lower limit of the
data went below the lower limit
input range. Or, the
of the output range.
analog output data
for output channel 6
went below the
lower limit of the
output range.
The analog input
• The analog input data went
data for input chan-
below the lower limit of the input
nel 7 went below
range. Or, the analog output
the lower limit of the
data went below the lower limit
input range. Or, the
of the output range.
analog output data
for output channel 7
went below the
lower limit of the
output range.
The analog input
• The analog input data went
data for input chan-
below the lower limit of the input
nel 8 went below
range. Or, the analog output
the lower limit of the
data went below the lower limit
input range. Or, the
of the output range.
analog output data
for output channel 8
went below the
lower limit of the
output range.
The event log was
• The event log was cleared by
cleared.
the user.
Meaning
Assumed cause
An error occurred in
• Non-volatile memory failure.
non-volatile mem-
ory.
An error occurred in
• Noise
the A/D converter
• A/D converter failure
The temperature
• There is a faulty connection to
cannot be con-
the cold junction sensor.
verted because the
• The cold junction sensor failed.
cold junction sensor
is disconnected.
An error occurred in
• There is an error in the area of
the control parame-
the non-volatile memory in the
ters that are saved
Communications Coupler Unit
in the master.
in which the control parameters
for the NX Unit are saved.
• The power supply to the NX
Unit was turned OFF or Sys-
mac Studio communications
were disconnected while writing
the control parameters.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
U
S
NX-series
Analog I/O
Units User's
Manual
(W522)
U
S
Same as
above.
U
S
Same as
above.
S
Same as
above.
Level
Maj
Prt
Min
Obs
Info
S
NX-series
Analog I/O
Units User's
Manual
(W522)
S
Same as
above.
S
U
Same as
above.
S
Same as
above.
Reference
3
Reference
3-97