Omron NX-series User Manual page 25

Safety network controller communication control unit built-in function
Hide thumbs Also See for NX-series:
Table of Contents

Advertisement

Term
Unit configuration information
safety application data
safety input function
safety output function
dual channel evaluation
single channel
dual channels
test pulse evaluation
change tracking
NX-series Communication Control Unit Built-in Function User's Manual (Z396)
The set of information that specifies the configuration of the NX Units that are connected to
the NX bus master.
On the Sysmac Studio, this is shown as configuration information and includes the I/O allo-
cation information.
The data that contains the settings that are used to operate the NX-series Safety Control
Units.
It consists of the safety programs, safety task, and variables. You use the Sysmac Studio to
create this data, and then transfer and execute it on the Safety CPU Unit.
On the Sysmac Studio, this data is shown as the slave parameters.
The location where the safety application data is stored on the Safety CPU Unit depends on
whether the safety programs have been validated. (Unvalidated safety programs are stored
in the main memory, while validated safety programs are stored in the non-volatile memory.)
A function that evaluates whether the signals that are input on a safety input terminal are
normal or abnormal.
Specific safety evaluation functions include test pulse evaluation and dual channel evalua-
tion.
When the evaluation result shows an abnormality, the safety input data is made inactive
(OFF).
A function that evaluates whether the values of safety output data and the output signals on
safety output terminals are normal or abnormal.
Specific safety evaluation functions include test pulse evaluation and dual channel evalua-
tion.
When the evaluation result shows an abnormality, the output signal on the safety output ter-
minal is turned OFF.
This function uses a pair of safety input or safety output terminals as redundant terminals
that are checked for consistency to evaluate the status of the safety input or safety output.
The input or output is used as a single point.
Two inputs or outputs are used as a pair of points for redundancy.
This function outputs a test pulse that is used to evaluate a safety input or safety output for
failures or wiring errors with the connected external device.
A pin is used to manage whether the safety application data has been changed after the fi-
nalized data is created.
Description
Terminology
23