Variable name
Meaning
_EIP2_EtnCfgErr
Port2 Basic Ethernet
Setting Error
_EIP_IPAdrCfgErr
IP Address Setting
Error
_EIP1_IPAdrCfgErr
Port1 IP Address
Setting Error
_EIP2_IPAdrCfgErr
Port2 IP Address
Setting Error
_EIP_IPAdrDupErr
IP Address Duplica-
tion Error
_EIP1_IPAdrDupErr
Port1 IP Address Du-
plication Error
_EIP2_IPAdrDupErr
Port2 IP Address Du-
plication Error
_EIP_DNSCfgErr
DNS Setting Error
NX-series Communication Control Unit Built-in Function User's Manual (Z396)
Function
Indicates that the Ethernet communica-
tions speed setting (Speed/Duplex) for
the communications port 2 is incorrect.
Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Indicates the IP address setting errors for
the communications port 1.
TRUE:
There is an illegal IP address setting.
A read operation failed.
The IP address obtained from the
BOOTP server is inconsistent.
FALSE: Normal
Indicates the IP address setting errors for
the communications port 1.
TRUE:
There is an illegal IP address setting.
A read operation failed.
The IP address obtained from the
BOOTP server is inconsistent.
FALSE: Normal
Indicates the IP address setting errors for
the communications port 2.
TRUE:
There is an illegal IP address setting.
A read operation failed.
The IP address obtained from the
BOOTP server is inconsistent.
FALSE: Normal
Indicates that the same IP address is as-
signed to more than one node for the
communications port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
Indicates that the same IP address is as-
signed to more than one node for the
communications port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
Indicates that the same IP address is as-
signed to more than one node for the
communications port 2.
TRUE: Duplication occurred.
FALSE: Other than the above.
Indicates that the DNS or hosts settings
are incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Appendices
Range of
Data type
values
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
Reference
page A - 66
page A - 67
A
page A - 67
page A - 67
page A - 68
page A - 68
page A - 68
page A - 68
A - 37