Omron NX-series User Manual page 134

Safety network controller communication control unit built-in function
Hide thumbs Also See for NX-series:
Table of Contents

Advertisement

8 CIP Message Communications
Instance ID
Specify 00 hex.
l Class Attribute ID
The class attribute ID specifies the attribute (value) of the entire object.
Attribute ID
Parameter name
01 hex
Revision
02 hex
Max Instance
65 hex
PLC Error Status
66 hex
PLC Model
l Instance Attribute ID
None
Request Paths (IOIs) to Specify Objects
When you specify an object, specify the request path (IOI) for each service code as given below.
Service code
0E hex
Get_Attribute_Single
10 hex
Set_Attribute_Single
8 - 38
Description
Revision of the object
The maximum instance num-
ber
Indicates when there is a
Controller error. Changes to
TRUE when a fatal or non-fa-
tal error occurs.
Indicates the model of the
Controller. The length is al-
ways 2 bytes for the size
+ 20 bytes for the name. Un-
used area is padded with
spaces.
Class
Instance ID
ID
C4 hex
00 hex
NX-series Communication Control Unit Built-in Function User's Manual (Z396)
Write/Read data
Attrib-
Data
ute
type
Read
UINT
Always 0002 hex
Read
UINT
Always 0001 hex
Read
UINT
0000 hex: There is no Con-
troller error.
0001 hex: There is a Con-
troller error.
Read
STRING
Specifies the attribute of the
class to read or write: 01 hex, 02
hex, or 64 to 66 hex
Value
Attribute ID

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx-csg series

Table of Contents