Omron NX-series User Manual page 207

Safety network controller communication control unit built-in function
Hide thumbs Also See for NX-series:
Table of Contents

Advertisement

Variable name
Meaning
_EIP1_PortErr
Communications
Port1 Error
NX-series Communication Control Unit Built-in Function User's Manual (Z396)
Function
This is the error status variable for the
communications port 1.
It represents the collective status of the
following error flags.
_EIP1_MacAdrErr (Port1 MAC Ad-
dress Error)
_EIP1_LanHwErr (Port1 Communica-
tions Controller Error)
_EIP1_EtnCfgErr (Port1 Basic Ether-
net Setting Error)
_EIP1_IPAdrCfgErr (Port1 IP Address
Setting Error)
_EIP1_IPAdrDupErr (Port1 IP Address
Duplication Error)
_EIP1_BootpErr (Port1 BOOTP Serv-
er Error)
_EIP_DNSCfgErr (DNS Setting Error)
_EIP_DNSSrvErr (DNS Server Con-
nection Error)
_EIP_IPRTblErr (IP Route Table Error)
Note If a Link OFF Detected or Built-
in EtherNet/IP Processing Er-
ror occurs, it is recorded in the
event log and then the corre-
sponding bit turns ON.
Refer to A-4-5 Meanings of Er-
ror Status Bits on page A - 52
for the meanings of the error
status bits.
Appendices
Range of
Data type
values
WORD
16#0000 to
16#00F0
Reference
page A - 62
A
A - 33