Honeywell SMV800 User Manual page 210

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Flow Calculation
Warning
Fault
Page 198
During setup and
Carefully review the
configuration of the
flow algorithm
flow
parameter
algorithm
values that have been
parameters,
configured. Correct
insufficient
any errors. When the
configuration
flow is showing a
or invalid parameter
good value and this
values have been
status is cleared,
entered
reset the device to
which are causing a
clear any Critical
division by zero math
Status that may have
error
been generated due
in the flow calculation
to the bad flow
calculation.
Parameters to check:
For Primary Elements
/ Algorithms other
than Pitot Tube
(Algorithm Option =
ASME 1989
Algorithms) and for
any Elements
(including Average
Pitot Tube, Algorithm
Option = Advanced
Algorithms)
Pipe Diameter D
cannot be equal to
Bore Diameter d
d must be > 0
D must be > 0
d < D
For primary element /
algorithm = Pitot Tube
(applicable to
Algorithm Option =
ASME 1989
Algorithms only)
Pipe Diameter D must
be equal to Bore
Diameter d
alpha_D must be
equal to alpha_d
D = d and alpha_D =
alpha_d
D and d must be > 0
alpha_D and alpha_d
must be > 0
Primary Element =
Wedge
Segment Height H <
D H and D > 0
Viscosity and Density
Coefficeints (as
applicable)
Make sure at least
one of the Viscosity
coefficients > 0
Make sure at least
one of the Density
coefficients > 0
SMV800 Modbus User's Guide
Bit - 5
119
Revision 1.0