Honeywell SMV800 User Manual page 202

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Meterbody
Failure
Sensor
Charactarization
corrupt
Pressure
Suspect Input
Sensor RAM DB
Fault
Details of
Critical
Fault
Pressure NVM
Corrupt
Sensor RAM
Corrupt
Sensor Code
Corrupt
Sensor Flow
Failure
Sensor Input
Failure
Page 190
Pressure module is
Power cycle the
reporting a critical
device. If the problem
failure of the
persists, replace the
pressure sensing
Meter Body
measurement within
the Meter Body,
which may be
caused by one of the
following:
• Meter body failure
• Sensor firmware
flow failure
Pressure module is
Power cycle the
reporting corruption
device. If the problem
in the Pressure
persists, replace the
Characterization data
Meter Body
Differential Pressure,
Verify that all inputs
Meter Body
are within
Temperature and/or
specifications. Power
Static Pressure input
cycle the device. If
are extremely out of
the problem persists,
range such that the
replace the Meter
value is suspect.
Body.
Pressure module is
Power cycle the
reporting corruption
device. If the problem
in the database in the
persists, replace the
Random Access
Meter Body
Memory (RAM)
Pressure module is
Power cycle the
reporting corruption
device and if fault is
of the Non-Volatile
cleared ensure to
Memory data (NVM)
configure sensor
parameters. If the
problem persists,
replace the Meter
Body
Pressure module is
Power cycle the
reporting corruption
device. If the problem
in the Random
persists, replace the
Access Memory
Meter Body
(RAM)
Pressure module is
Power cycle the
reporting corruption
device. If the problem
in sensor firmware
persists, replace the
Meter Body
Pressure module
Power cycle the
firmware Program
device. If the problem
Flow Failure. This
persists, replace the
fault will get set if any
Meter Body
of the critical part of
the code is not
executed after
expected duration.
The temperature
Check the
sensor
temperature sensor
(Thermocouple or
connections for
RTD) has an open
disconnections or
input. The sensor
broken wires. Repair
connections may
the sensor
be disconnected or
connections
broken.
SMV800 Modbus User's Guide
Bit - 0
Bit -1
Bit - 2
Bit - 3
116
Bit - 4
Bit - 5
Bit - 6
Bit - 7
Bit - 8
Revision 1.0