Honeywell SMV800 User Manual page 167

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Transmitter
408
status3
Transmitter
409
status4
PT Hi Alarm
411
Counter
PT Lo Alarm
413
Counter
PT High Val &
415
TimeStamp
PT Low Val &
417
TimeStamp
Temp Sensor
419
Install Date
Temp Sensor
421
Time In
Service
Revision 1.0
Third byte of transmitter
status
Fourth byte of transmitter
status
The total number of minutes
that the Process Temperature
input has exceeded the PT
High Alarm Limit.
The total number of minutes
that the Process Temperature
input has been below the PT
Low Alarm Limit.
Displays the highest
recorded value of Process
Temperature and
the time elapsed since the
Process Temperature last
exceeded the
PT High Alarm Limit.
Displays the lowest recorded
value of Process Temperature
and the time elapsed since
the Process Temperature last
dropped below the
PT High Alarm Limit.
One time temperature
sensor installation date.
Percent of the expected
Service Life that the
Temperature Module has
been in service. Value is
based on electronics
temperature. Service life
accumulates faster at higher
temperatures with an
exponential relationship.
SMV800 Modbus User's Guide
RO
uint8
Bit0: reserved
Bit1: 0 = Off; 1 = Write
Protect enabled
Bit2: 0 = Off; 1 = flow pv4
simulation enabled
Bit3: 0 = Off; 1= pt pv3
simulation enabled
Bit4: reserved
Bit5: reserved
Bit6: reserved
Bit7: 0 = Off; 1 = sp pv2
simulation enabled
Bit8: 0 = Off; 1 = dp pv1
simulation enabled
Bit9: reserved
Bit10: reserved
Bit11: reserved
Bit12: reserved
Bit13: reserved
Bit14: 0 = Off; 1 =
brownout reset
Bit15: 0 = Off; 1 = sensor
communication failure
uint8
RO
uint32
RO
uint32
RO
uint32
RO
uint32
R/W
uint32
RO
uint32
Reserved
N/A
N/A
N/A
N/A
N/A
N/A