Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Process
117
Variables
Status
Warnings
118
Status 1
Revision 1.0
Process Variables limits
status
Warnings Status 1
SMV800 Modbus User's Guide
RO
uint8
Bit - 0 Bad DP
Bit - 1 Bad MBT
Bit - 2 Bad SP
Bit - 3 Bad PT
Bit - 4 Bad Flow
Bit - 5 Bad Totalizer
Bit - 6 Differential pressure
measured is above URV
Bit - 7 Differential pressure
measured is below LRV
Bit - 8 Static pressure
measured is above URV
Bit - 9 Static pressure
measured is below LRV
Bit - 10 Process
Temperature measured is
above URV
Bit - 11 Process
Temperature measured is
below LRV
Bit - 12 Meter body
Temperature measured is
above URV
Bit - 13 Field Meter body
Temperature measured is
below LRV
Bit - 14 Field Flow
measured is above URV
Bit - 15 Field Flow
measured is below LRV
RO
uint8
Bit - 0 Communication
Section Non-Critical
Failure
Bit - 1 Sensing Section NC
Failure
Bit - 2 CJ Out Of Limit
Bit - 3 No Factory
Calibration
Bit - 4 Sensor Unreliable
Communication
Bit - 5 Tamper Alarm
Bit - 6 Low Supply Voltage
of Temp/MBT
Bit - 7 Device Warm Reset
Bit - 8 Display
Communication Failure
Bit - 9 Display NVM
Corrupt
Bit - 10 Communication
Module VCC Failure
Bit - 11 Communication
Supply Failure
Page 137