Honeywell SMV800 User Manual page 208

Multivariable transmitter modbus communication
Hide thumbs Also See for SMV800:
Table of Contents

Advertisement

Device Warm
Reset
Display
Communication
Failure
Warning
Display NVM
Corrupt
Communication
Module VCC
Failure
Transmitter
Supply Failure
Page 196
The supply voltage to
Power cycle the
the transmitter
device. If problem
terminals has
persist, Check the
dropped low enough
terminal voltage to be
to cause a warm
within limits. If still
reset of device
problem persists
replace the Terminal
block assembly. If
problem continues
replace the
Communication
module
Display
Secure Display
communication
connections and
failure
recheck. If problem
persists, reset the
device. If the problem
still persists, replace
the Display module.
Communication
Power cycle the
module is reporting
device. If the problem
corruption of the
is not seen, verify the
Non-Volatile Memory
parameters for
data (NVM) related to
configuration changes
display screen
made. If the problem
configuration.
still persists then
NVM might be
damaged so need to
replace Comms
board.
The voltage supply to
Power cycle the
the Communication
device. If problem
Module processor is
persist, Check the
outside the
terminal voltage to be
operational range of
within limits. If
2.8 to 3.2volts
problem continues
replace the Comms
module
Power Supply failure
Power cycle the
device. If problem
persist, Check the
terminal voltage to be
within limits. If still
problem persists
replace the Terminal
block assembly. If
problem continues
replace the Comms
module
SMV800 Modbus User's Guide
Bit - 7
Bit - 8
118
Bit - 9
Bit - 10
Bit - 11
Revision 1.0