PARAMETER SETTINGS

5.1.6 Valid module during other station access

5 - 31
This parameter is used to specify any of the following modules to be relayed when a
data communication request for which the network No. of the access target
programmable controller station cannot be specified from the host (access from the
serial communication module (A compatible 1C frame), Ethernet module (A compatible
1E frame), etc. to other stations) is issued.
• CC-Link IE Controller Network, CC-Link IE Field Network, MELSECNET/H,
MELSECNET/10 module
• Ethernet module
This setting is not required when a data communication request for which the network
No. can be specified, such as the serial communication module (QnA compatible 3C
frame, QnA compatible 4C frame) or Ethernet module (QnA compatible 3E frame), is
used. Leave it as the default (1) setting.
For details of the serial communication module or Ethernet module protocol, refer to
the MELSEC-Q/L MELSEC Communication Protocol Reference Manual.
[Screen settings]
(Example)
In the example below, the personal computer connected to the serial communication
module can communicate with the station on network No. 2 where the network module
3 is connected.
Valid module during
other station access: 3
Power
QCPU
QX41
QX41
supply
module
Select from the selection dialogue box.
A compatible 1C frame
Module 1
Module 2 Module 3 Module 4
QY41P
QJ71
QJ71
QJ71
LP21
E71
C24
-100
Network No. 1
Ethernet
MELSEC-Q
QJ71
QJ71
LP21
LP21
Network No. 3
Network No. 2
Power
QCPU
QJ71
supply
LP21
module
5 - 31