Chapter 8 Communications

8.3 MODBUS Communication Protocol

There are two modes of MODBUS networks communication, ASCII (American Standard
Code for information interchange) mode and RTU (Remote Terminal Unit) mode. Users
could set the needed communication protocol via parameter P3-02. Apart from these two
communication modes, this servo drive also supports function of 03H to access more than
one data, 06H to write one character and 10H to write multiple characters. Please refer to
the following descriptions.
 Code Description:
ASCII Mode:
The so-called ASCII mode is using American Standard Code for Information Interchange
(ASCII) to transmit the data. Between two stations (Master and Slave) to transmit data 64H,
the master will send '6' which represented by 36H of ASCII code and '4' represented by
34H of ASCII code.
The following table shows the available hexadecimal characters and their corresponding
ASCII code of digit 0 to 9 and characters A to F is as follows:
Character
'0'
ASCII code
30H
Character
'8'
ASCII code
38H
RTU Mode:
Every 8-bit of data is constituted by two 4-bits hexadecimal characters. If data 64H is
transmitted between two stations, it will be transmitted directly, which is more efficient than
ASCII mode.
 Character Structure
Characters will be encoded into the following framing and transmitted in serial.
The checking method of different bit is as the following.
10-bit character frame (For 7-bits character)
7N2
Start
bit
8-6
'1'
'2'
31H
32H
'9'
'A'
39H
41H
0
1
2
7-data bits
10-bits character frame
'3'
'4'
'5'
33H
34H
35H
'B'
'C'
'D'
42H
43H
44H
3
4
5
'6'
'7'
36H
37H
'E'
'F'
45H
46H
Stop
Stop
6
bit
bit
Revision May, 2018