Wire Type Rating; Terminal Tightening Torques - Trane VLT AQUA Drive FC 202 VLT AutomationDrive FC 301 Instruction Manual

Vertical bypass/non bypass panel
Table of Contents

Advertisement

Installation
HP (KW)
UL Motor Current
15 (11)
21
20 (15)
27
25 (18.5)
34
30 (22)
40
40 (30)
52
50 (37)
65
60 (45)
77
75 (55)
96
100 (75)
124
125 (90)
156
HP (KW)
UL Motor Current
15 (11)
17
20 (15)
22
25 (18.5)
27
30 (22)
32
40 (30)
41
50 (37)
52
60 (45)
62
75 (55)
77
100 (75)
99
125 (90)
125
Table 3.10 Wire Size Chart 460 and 600 V

3.4.4 Wire Type Rating

The wire style rating specifications are provided inTable 3.9 and Table 3.10

3.4.5 Terminal Tightening Torques

Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.12
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.
See Table 3.14 for a sample of the torque and wire rating data.
Vertical Bypass/Non Bypass Panel
460 V AC
Panel
(FC102/202/322)
Panel (FC302) Non
Non Bypass &
Bypass
Bypass
P2
P2
P3
P3
P4
P4
P5
P5
600 VAC
Panel
(FC102/202/322)
Panel (FC302) Non
Non Bypass &
Bypass
Bypass
P2
P2
P3
P3
P4
P4
P5
P5
®
MG.13.A1.22 - VLT
is a registered Danfoss trademark
Maximum Field
Field Ground
Wiring Size Class
Wiring Size Class
B or C
B or C
10 AWG
10 AWG
8 AWG
10 AWG
6 AWG
10 AWG
6 AWG
10 AWG
4 AWG
10 AWG
3 AWG
8 AWG
1 AWG
8 AWG
1 AWG
8 AWG
2/0 AWG
6 AWG
3/0 AWG
6 AWG
Maximum Field
Field Ground
Wiring Size Class
Wiring Size Class
B or C
B or C
10 AWG
10 AWG
10 AWG
10 AWG
8 AWG
10 AWG
8 AWG
10 AWG
6 AWG
10 AWG
4 AWG
10 AWG
3 AWG
8 AWG
1 AWG
8 AWG
1 AWG
8 AWG
2/0 AWG
6 AWG
Minimum
Temperature Wire
Rating "°C" Copper
Conductor
60
60
3
60
60
60
60
60
60
75
75
Minimum
Temperature Wire
Rating "Degree C"
Copper Conductor
60
60
60
60
60
60
60
60
60
75
3-21
3