Activate Zone-Address In Alarm Mode (H8/S8) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
31.8
Action
"Access"
Scroll to menu H8.
"A"
Scroll to menu S8.
"A"
Write the zone and
address, e.g. "12-45"
"A"
"Return"
Write another zone and
address, e.g. "12-34".
"A"
Rev: -
Activate zone-address in alarm mode
(H8/S8)
One alarm point (zone-address), not a whole zone, can be manually
activated, i.e. be set in alarm mode.
NOTE! All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will be
activated by this "manually activated" alarm as well.
Text in display
Maintenance
Acknowledge SERVICE signal
Activate zone/address in alarm mode
Select zone: 00
Select zone: 12
001 ZONE-ADDR 12-45 LAST ZONE 12
"Alarm text for 12-45"
Select zone: 00
Select zone: 12
001 ZONE-ADDR 12-45 LAST ZONE 12
"Alarm text for 12-45"
EBL128 Operating Instructions V2.0.x
ACCEPT? H8
ACCEPT? S1
ACCEPT? S8
address: 00
ACCEPT?
address: 45
ACCEPT?
No. 01
address: 00
ACCEPT?
address: 34
ACCEPT?
No. 01
133
Comments
According to chapter
"Access", see page 81.
Press "A" to accept /
activate the fire alarm.
Normal fire alarm
presentation in the
EBL128 / FBP display.
If more alarm points have
to be set in alarm status,
press "Return" to select
another zone - address and
continue as above.
Press "A" to accept / start
the fire alarm.
The LEDs "Alarms
queued" (L2) are
indicating that more than

Hide quick links: