Re-Enable Output (H2/B7) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.7
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B7.
"A"
"0", "1", "2" or "3"
"A"
Depending on the
chosen type the
following will be
shown:
"A"
"Return"
Rev: -

Re-enable output (H2/B7)

Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
If there is nothing to re-enable, --- List is empty --- will be
shown.
Text in display
Disable or re-enable
Disable zone
Re-enable output
Re-enable output type: 0
0=Loopunit 1=S 2=R0 3=EXPB
Or, e.g. if only type 2 is disabled:
Re-enable output type: 0
2=R0
Re-enable output 0 technical address 000
Re-enable output S0
Re-enable output R0
Re-enable output 0 expansion board 0
--- List is empty ---
Re-enable output
73
Expansion board (EXPB) 0-3,
4581: Relay output 0-7 alt. 4583: Output 0-2.
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B7
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? B7
93
Comments
According to chapter
"Access", see page 81.
Only disabled type(s) will
be shown. Press:
"0"=3361 or 3377/4477 or
3379 or 3364 or 4380 or
4383
"1"=C.i.e. output S0-S1
"2"=C.i.e. output R0
"3"=C.i.e. exp. board
73
output.
Press "A" to accept.
L=A list in which you can
L
scroll.
Regarding the 3377/4477
L
& 3379 units' output no.:
0=high priority
1=medium priority
L
2=low priority
Press "A" to accept.
L
All types are re-enabled.
If more re-enabling shall
be done, continue like