Panasonic EBL128 Operating Instructions Manual page 80

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
Action
66
Power down
up again. ("Cold restart")
Via menu H8/S4 Safe shut down
of control unit. ("Cold restart")
Automatically after download of
site specific data (SSD) via a PC
& EBLWin. ("Warm restart")
Automatically after download of
S/W via a PC & EBLWin. ("Cold
restart")
Automatically due to external
67
disturbance.
("Cold restart")
Data, etc.
which will be
deleted
and then power
SSW
FFD, WASV
FFD, WASV
FF, WASV, D
FFD, WASV
FFD, WASV
NOTE! During the restart, the output "R1" for Fault tx will be
"activated", the supervised 24 V DC outputs S0-S1 will be not
supervised and S0-S1 programmed as normally high will be low for a
few seconds.
During the "restart", no fire alarm can be activated and the buzzer will
sound until the following text messages is show in the display:
*** EBL128 ***
Checking program memory......
And for a second (if everything is all right, else see Memory fault
below):
Booting......
A fault is now generated and the following text message will be
shown in the display:
FAULT: Restart code xx addr yyyy
Date: MM-DD
Time: HH:MM
Regarding code xx and yyyy, see also page 67. This fault is also
indicated by LEDs "Fault tx activated" (L11) and "General fault" (L7).
After the fault is acknowledged (via menu H6), the LEDs will be
turned OFF if there are no other faults.
66
Power supply (mains) and battery disconnected.
67
If this happens often, call for service personnel / engineer.
78
EBL128 Operating Instructions V2.0.x
Data, etc.
Restart code
which will be
not deleted
SSD,
S/W
SSD,
S/W, SSW
SSD,
S/W, SSW
SSD,
S/W, SSW
SSD,
S/W, SSW
00
00 alt. 03
25
03