Activate Output (H8/S9) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
31.9
Action
"Access"
Scroll to menu H8.
"A"
Scroll to menu S9.
"A"
Depending on if 0, 1, 2
or 3 is selected one of
the alternatives will be
shown.
"A"
Depending on if 0, 1, 2
or 3 is selected one of
the alternatives will be
shown.
"A"
"Return"
Rev: -

Activate output (H8/S9)

Any output can be activated via this menu (H8/S9).
NOTE! It will be activated until reset via menu H8/S10.
Text in display
Maintenance
Acknowledge SERVICE signal
Activate output
Activate output type: 0
0=Loopunit 1=S 2=R0 3=EXPB
Activate output: 0, technical address 000
Activate S0
Activate R0
Activate output: 0, expansion board 0
Output 0 technical address 002
forced active
Output S0 forced active
Output R0 forced active
Output 0 expansion board 0 forced active
Activate output type: 0
0=Loopunit 1=S 2=R0 3=EXPB
EBL128 Operating Instructions V2.0.x
ACCEPT? H8
ACCEPT? S1
ACCEPT? S9
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
135
Comments
According to chapter
"Access", see page 81.
Loop unit=3361 or 3364
S=S0-S1
R0=R0
EXPB= 4581 or 4583
Fill in the requested data
respectively and press
"A".