Re-Enable Zone (H2/B5) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.5
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B5.
"A"
"A" (to re-enable)
or
"Return"
"Return"
Rev: -

Re-enable zone (H2/B5)

Disabled zones are listed in menu H4/U1.
Re-enabling via this menu (H2/B5) has higher priority than automatic
re-enabling.
Zones disabled when the "New Zealand FB Silence switch" (outside
switch) is turned OFF, have to be re-enabled via menu B5 or B6
before they can activate a new alarm.
When all zones have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
NOTE! Alarm points that have been individually disabled via menu
H2/B2 cannot be collectively re-enabled via this menu. They have to
be individually re-enabled.
If there is nothing to re-enable, --- List is empty --- will be
shown.
Text in display
Disable or re-enable
Disable zone
Re-enable zone
Re-enable zone: 01
Re-enable zone
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B5
ACCEPT?
ACCEPT? B5
ACCEPT? H2
91
Comments
According to chapter
"Access", see page 81.
L=A list in which you can
L
scroll.
Press "A" to accept. You
will stay in this list until all
zones are re-enabled or
press "Return" to menu
B5.
If more re-enabling shall
be done, continue like
above. If not, scroll or
press "Return" to menu
H2.
Scroll or press "Return"