Reset of a week average sensor value

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
set to the default value. If not, the new / clean sensor will inherit the
old / dirty sensor's week average sensor value.
It is possible to clear the week average sensor value for each sensor
individually, see chapter "Restore weekly average to default (H8/S5)",
page 130. See also chapter "Acknowledge SERVICE signal (H8/S4)",
page 129.
NOTE! Authorised service personnel only, must do the reset to
default value. Used incorrectly it can cause nuisance fire alarms.