Display Current Consumption On Com-Loop (H5/A5) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
28.5
Action
"Access"
Scroll to menu H5.
"A"
Scroll to menu A5
"A"
"A"
or
"Return"
"Return"
Rev: -
Display current consumption on COM-loop
(H5/A5)
An average current consumption value can be displayed for the COM
loop.
NOTE! No or very small current consumption will not be presented
correctly / precisely since the accuracy is ± 5 mA.
Text in display
Service
Calibration of supervised outputs
Display current consumption on
COM-loop
Current consumption on COM-loop is
xxx mA
Display current consumption on
COM loop
Service
NOTE! The window is updated continuously.
EBL128 Operating Instructions V2.0.x
ACCEPT? H5
ACCEPT? A1
ACCEPT? A5
ACCEPT?
ACCEPT? A5
ACCEPT? H5
118
Comments
According to chapter
"Access", see page 81.
Scroll or press "Return" to
H5.
Scroll or press "Return"